• +92 (021) 35391031-32

  • info@aljibra.com

default-logo

Components

 Beam detector:  refective optical beam smoke detector with a motorized head, capable of aligning itself automatically during the commissioning phase and of re-aligning itself during service.  The system comprises a motorized head unit containing an infra-red transmitter and receiver, a ground level controller and prism refector. The presence of Smoke is revealed by the analysis of the returned infrared beam thus allowing the system to detect fre in its early stages.
Operational adjustments can be made from ground level by means of the controller unit. The standard protection system covers a range of 5 to 40 meters. Range-expander kits are also available: a 40 to 80 meter kit which uses 4 refectors and an 80 to 100 meter kit which uses 9 refectors.
Commission:  the beam alignment phase is an extremely simple procedure. In fact, the beam
aligns itself on the centre of the refector..Adjust thresholds: the beam detector sensitivity is fully adjustable between 25 and 50% of beam obscuration.

Check contamination compensation:  the beam detector automatically compensates for dust build up on the lenses. You can check the status of the device on the display and need clean the lenses only when required.

Alarm and fault delay: the alarm delay can be set at 1 and 30 seconds (in steps of 1 second), whereas the Fault delay can be set at 1 to 60 seconds.

Change latching mode:  the beam detector relays can be set to latch on alarm or auto reset depending on application requirements.

Turn on and off: the beam detector can be switched of from the control panel. Should you forget to turn it back on, it will resume normal operation after 8 hours.

Self test: the beam detector can be tested from ground level as part of routine maintenance.

IP65: the enclosure is IP65 rated. The device is fully sealed, therefore, is suitable for installation in unfriendly (dusty or dirty) environments and can even be pressure washed.

Technical features
Enclosure White high heat abs UL94 HB Quiescent current 3 mA
Enclosure rating IP65 Alarm current 3 mA
Operating temperature -15°C / +55°C Alarm latching Non latching option
Time to fault Adjustable between 1 and 60s Fault relay 1A at 30 V
Time to fire Adjustable between 1 and 30s Fire relay 1A at 30 V
Sensitivity  Fully adjustable between 25% & 50% Dimensions (WxHxD 155 x 180 x 125mm
Operating voltage 10.2 / 30 V Weight  Head 1kg; Controller 0.5kg