• +92 (021) 35391031-32

  • info@aljibra.com

default-logo

Characteristics

  • Special chamber design has greatly decreased dust levels and improved detection accuracy.
  • Dual LEDs for 360-degree visibility.
  • Advanced technology enables this detector to increase its precision in fire detection, improve signals to avoid noise interference and thus reduce unwanted false alarm.
  • Low current consumption that allows more detectors to be used with each control panel.
  • Dual contacts on the base which enhance the connecting stability between sensor and base.
  • All bases are fitted with a shorting spring to permit maintenance without disconnecting when removing the detector head.

Multi-purpose Resettable Type

This unit has designed for relay output feature with optional individual power source and it has been used widely in the current market. This resettable detector is not only use as a fire alarm system but will also supervise input power via an optional relay output for power breakdown or wire break. Fault relay contact will open when power breakdown occur and fire alarm signal will transmitted to connected system or computer terminal when detector is activated. When the alarm signal is absent the detector will automatically return to standby status. Optional built-in buzzer can sound a warning at the first sign of fire. This detector is currently used quite often in security systems and is also promoted for use in communications, banking, shipping or the art business.


Specifications

Model
AH-0316-2
AH-0316-3
AH-0316-4
Voltage Range
12 ~ 30V DC
Standby Current
45μA
Alarm Current
@24V DC 470Ω
30mA
35mA
40mA
Thermal Setting
58℃
Response Grade
Comply to EN54, Grade 1
Ambient Temperature
-10℃ ~ +55℃
Material
Fire-proof plastic
Dimensions
102mm(Dia.) x58mm(H)
Weight
145g
147g
160g
Color
White

 

Order information

AH-0316-2
2-wire
AH-0316-3
3-wire with remote indicator output
AH-0316-4
4-wire with relay output

 

Specifications (Resettable)

Model
AH-0316-S
Alarm Current
35mA
Standby Current
30μA
Voltage Range
12V DC
Weight
157g

 

Order Information (Resettable)

AH-0316-S
+ Relay Output

 

Effective alert area

Construction/Height
Under 4M
4M ~ 8M
Fire-proof Building
90 M2
45 M2
Ordinary Building
50 M2
30 M2
Approval